BV-D RESIDUAL CURRENT DEVICE

ELECTRICAL
Design according to
IEC 1008 (EN61008)
Tripping time
undelayed
min.10ms delay
min.40ms delay
with selective disconnecting function
Rated voltage
230/400V;50Hz
Rated tripping current
10,30,100,300,500mA
Sensitivity
AC and pulsating DC
Rated short
10KA with 63a gl back-up fuse
Circuit strenth
10KA with 80A gL (F7-80 and -863)
6KA (rated current 63A) with 63A gL
Maximum back-up fuse for
63gL
short circuit protection
80A gL(F7-80 and -863)
maximum back-up fuse for
45A gL(F7-25 and -40A)
Overload protection
40A gL(F7-80A)
Resistance to climatic conditions
according to IEC 1008
Degree of protection
built-in switch IP 40
Endurance electrical comp. mech comp
≤4.000 operating cycles
≥20.000 operating cycles
MECHANICAL
Frame size
45mm
Socket size
80mm
Device width
35mm(2mod.), 70mm(4mod.)
Mounting
quick fastening with 2 lock-in positions on DIN rail En50022
Upper and lower terminals
Open mouthed/lift terminals
Terminal protection
Finger and hand touch sage, VBG5, OVE-EN 6
Terminal capacity
1--25mm2
Busbar thickness
0.8-2mm
 